Features :

  • Wide Input Voltage Range
  • Galvanic Isolation
  • Internal Static & Manual Maintenance bypass switch
  • Redundant Parallel Architecture (up to 8 units)
  • High Efficiency
  • Intelligent automatic battery test (every 24 hours)
  • Designed for any kind of application (industrial loads)
  • Simple to install
  • Manufacturing in Italy
  • Multi Modul Boards

Technical Data NM Series

MODEL NM 10 NM 15 NM 20 NM 30 NM 40 NM 60 NM 80 NM 100
INPUT
Rated Voltage 400 Vac three-phase
Voltage range (Vac) ± 20%
Frequency range (Hz) 45 ÷ 65 Hz
Power factor > 0.92 with harmonic filter
Current harmonic distortion < 5% with harmonic filter
Soft start 0-100% in 10”
BY PASS
Rated Voltage
230 Vac Single - phase
Permitted voltage range
± 15% (selectable from ± 10% to ± 25% from front panel)
Rated Frequency (Hz) 50 / 60 Hz
Permitted frequency range
± 2% (selectable from ± 1% to ± 5% from front panel)
Standard features
Back Feed protection; split bypass line
BATTERIES
Type Type maintenance-free lead-acid VRLA AGM / GEL; NiCd
Maximum recharge current
0,2xC10
AC ripple voltage <1%
INVERTER OUTPUT
Rated power (kVA)
10
15 20 30 40 60 80 100
Active power (kW)
9 13,3 18 27 36 54 72 90
Number of phases
1
Rated voltage
230 Vac single-phase
Regulation of the output voltage
220 ÷ 244 Vac phase/neutral (from control panel)
Crash factor (lpeak/lmrs)
3 : 1
Static stability ± 1%
Dynamic stability ± 5%
Frequency 50/60 selectable
Overload 110% 125% 150% of the rated current for 5h/10’/1’
Frequency stability ± 0,05% on mains failure± 2% (selectable from ± 1% to ± 5%) with mains supply present
SYSTEM
Weight 200 220 230 290 340 440 520 650
Dimensions(wdh)(mm) 555x740x1400
800x740x1400
800x800x1900
Remote signaling
Volt free contacts
Remote Controls EPO and Bypass
Communication RS232 + remote contacts
Operating temperature 0° C - 40° C
Relative humidity <95%non condensing
Color Light grey (RAL 7035)
Noise 54 dBA
60 dBA
Protection degree IP 20
Efficiency >92%
Compliance Safety EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3
Internal batteries Yes Yes Yes No No No No No


Technical Data NT Series

MODEL
NT 10
NT20 NT 30 NT 40 NT 60 NT 80 NT 100 NT 120 NT 160 NT 200 NT300
INPUT
Rated Voltage 400 Vac three-phase
Voltage range (Vac) ± 20%
Frequency range (Hz) 45 ÷ 65 Hz
Power factor > 0.92 with harmonic filter
Current harmonic distortion < 5% with harmonic filter
Soft start 0-100% in 10”
BY PASS
Rated Voltage
400 Vac Three phase
Permitted voltage range
± 15% (selectable from ± 10% to ± 25% from front panel)
Rated Frequency (Hz) 50 / 60 Hz
Permitted frequency range
± 2% (selectable from ± 1% to ± 5% from front panel)
Standard features
Back Feed protection; split bypass line
BATTERIES
Type Type maintenance-free lead-acid VRLA AGM / GEL; NiCd
Maximum recharge current
0,2xC10
AC ripple voltage <1%
INVERTER OUTPUT
Rated power (kVA)
10 20 30 40 60 80 100 120 160 200 300
Active power (kW)
9 18 27 36 54 72 90 108 144 180 270
Number of phases
3 + N
Rated voltage
400 Vac Three phase
Regulation of the output voltage
348 ÷ 424 Vac phase/neutral (from control panel)
Crash factor (lpeak/lmrs)
3 : 1
Static stability ± 1%
Dynamic stability ± 5%
Frequency 50/60 selectable
Overload 110% 125% 150% of the rated current for 5h/10’/1’
Frequency stability ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5%) with mains supply present
SYSTEM
Weight 212
230 280 330 450 600 640 650 770 810 1400
Dimensions(wdh)(mm) 555x740x1400
800x740x1400 800x800x1900
1500x1000x1900
Remote signaling
Volt free contacts
Remote Controls EPO and Bypass
Communication RS232 + remote contacts
Operating temperature 0° C - 40° C
Relative humidity <95%non condensing
Color Light grey (RAL 7035)
Noise 54 dBa 60 dBa 62 dBa 63-68 dBA
Protection degree IP 20
Efficiency >92%
Compliance Safety EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3
Internal batteries Yes
Yes Yes No No No No No No No No

Technical Data NT IGBT Series

MODEL NT 100 NT 120 NT 160
NT 200
NT 250 NT 300
NT 400 NT 500
INPUT
Rated Voltage 400 Vac three-phase
Voltage range (Vac) ± 20%
Frequency range (Hz) 45 ÷ 65 Hz
Power factor > 0.99
Current harmonic distortion < 3 % THDI
Soft start 0-100% in 30”
BY PASS
Rated Voltage
400 Vac Three - phase
Permitted voltage range
± 15% (selectable from ± 10% to ± 25% from front panel)
Rated Frequency (Hz) 50 / 60 Hz
Permitted frequency range
± 2% (selectable from ± 1% to ± 5% from front panel)
Standard features
Back Feed protection; split bypass line
BATTERIES
Type Type maintenance-free lead-acid VRLA AGM / GEL; NiCd
Maximum recharge current
0,2xC10
AC ripple voltage Zero
INVERTER OUTPUT
Rated power (kVA)
100
120 160 200 250 300 400 500
Active power (kW)
90 108 144 180 225 270 360 450
Number of phases
3 + N
Rated voltage
400 Vac single-phase
Regulation of the output voltage
348 ÷ 424 Vac phase/neutral (from control panel)
Crash factor (lpeak/lmrs)
3 : 1
Static stability ± 1%
Dynamic stability ± 5%
Frequency 50/60 selectable
Overload 110% 125% 150% of the rated current for 60’/10’/1’
Frequency stability ± 0,05% on mains failure± 2% (selectable from ± 1% to ± 5%) with mains supply present
SYSTEM
Weight 656 700 800 910 1000 1400 1700 2100
Dimensions(wdh)(mm) 800x850x1900 1000x850x1900 1500x1000x1900 2100x1000x1900
Remote signaling
Volt free contacts
Remote Controls EPO and Bypass
Communication RS232 + remote contacts
Operating temperature 0° C - 40° C
Relative humidity <95%non condensing
Color Light grey (RAL 7035)
Noise 63 - 68 dBA
70 - 72 dBA 72 dBA
Protection degree IP 20 ( others upon request )
Efficiency >92%
Compliance Safety EN 62040-1 EMC EN 62040-2 Directives 73/23-93/68-89/336 EEC EN 62040-3
 