Online UPS
|
Features
- On Line Double Conversion
- Super Wide Input Voltage Range Without Using Battery
- N + 1 Redundancy Parallel Function ( 6-10Kva )
- Advance IGBT Power Components
- Controlled By Fully Digitized Microprocessor
- High Input Power Factor
- Self Diagnosis and Protection
- Smart RS 232 / USB Communication and Compatible with SNMP
- Large LCD and LED Display
- Pure Sine wave Output
Technical Specifications L Series
MODEL
|
L 1000 |
L 2000
|
L 3000 |
L 6000 |
L 10K |
|
INPUT
|
|
Voltage (Vac) |
Half load 110 - 300 Vac, Full Load 165 - 300 Vac |
Frequency (Hz) |
45.5 - 54.5 Hz (adjustable) |
Phase |
Single |
Power Factor |
> 0.95 |
|
OUTPUT |
|
Capacity (Va/W) |
1000/700 |
2000/1400 |
3000/2100 |
6000/4800 |
10K/7KW |
Voltage (Vac) |
220 V
|
Voltage Regulation |
± 2% |
Frequency (Hz) |
50 / 60 Hz ± 0.5 |
Waveform |
Pure Sine Wave, THD <3% at 0-100 load% |
Transient Response |
± 4% (100% Load Variation) |
Power Factor |
0.7 |
Transfer time
|
0 Ms |
Crest Factor |
3 : 1 |
Efficiency (AC - AC) |
> 85% |
DC Start |
Yes |
Back Up Time (full load) |
10 minutes |
|
PROTECTION |
|
EMI/RFI Filter |
10-100 KHz at 40 db,100KHz-100MHz at 70 db
|
Overload |
110 % - 150% Switch to Bypass after 1 Min;>150% Shutdown after 200ms
|
UPS Fault |
By pass, load supplied from mains less than 2 msec |
Short Circuit |
UPS turn off output and alarm |
Battery |
Battery Low Shutdown |
Spike Protection |
EN 61000 4-5 |
|
BATTERY |
|
Type
|
12 V Seal Lead Acid Battery, maintenance free |
Voltages (Vdc) |
36 |
96 |
240 |
Quantity (pcs) |
3 |
8 |
20 |
Charging |
8 hours to 90% capacity |
|
OTHERS |
Communication Interface |
RS 232 , USB and SNMP ( Optional ) |
LED and LCD |
Utility, Inverter, Bypass, Battery, Battery Mode, Frequency, UPS Fault Indicator |
UPS Abnormal |
Continuous Beep and Red LED On |
Noise Level |
< 55db |
Ambient Temperature |
0°C - 40°C |
Humidity |
10% - 90% |
|
PHYSICAL |
|
Dimension (WxDxH) mm |
145x415x215 |
190x470x330 |
260x560x730 |
Weight (kg) |
12.5 |
28 |
30 |
86 |
90 |
|